 Features
 For measuring relative air humidity and temperature
 Measurement throughout the humidity range of 0 to 100 % RH
 Intelligent interchangeable probes for simple replacement
 For operating temperatures between -40 and +80 °C
 Option of separate probes for humidity and temperature
 2 m, 5 m, or 10 m adapter cable for probe extension
 Robust metal housing, suitable for clean rooms
 Integrated LCD display (optional)
 With standardized current or voltage outputs
 
 Specification: 
 
 
    
        
            | Sensing element | Type: HC105 capacitive (SMD version, condensation permitted), largely maintenance free in normal, clean air
 |  
            | Measuring/working range | 0 to 100% rH |  
            | Medium | air, unpressurized, not corrosive |  
            | Accuracy (incl. hysteresis, non-linearity and repeat accuracy) | ±(1.5 + 0.5% x measured value) % rH; (at <90% rH; -15 to +40°C) 2.5% rH;                                             (at >90% rH; -15 to +40°C)
 ±(1.7 + 1.5% x measured value) % rH; (at -40 to +80°C)
 The tolerance data includes the uncertainty of the factory calibration with an expansion factor k = 2 (double the standard deviation). The tolerance is calculated to EA-4/02, taking GUM (Guide to the Expression of Uncertainty in Measurement) into consideration.
 |  
            | Temperature dependence of the electronics | ±0.006% rH/°C |  
            | Response time rH (with stainless steel mesh filter) | typ. <15s                                             (at 20°C/t0.9) |  Temperature
 
    
        
            | Sensing element | Pt1000 thin film temperature sensor tolerance class A to DIN EN 60 751
 |  
            | Measuring range | -40 to +60°C, measurement probes directly on the hygrothermal transducer -40 to +80°C, remote measurement probes, by means of the adapter cable
 |  
            | Measuring accuracy |  |  
            | Temperature dependence of the electronics | ±0,007°C/°C |  
            | Response time T (with stainless steel mesh filter) | typ. <3mins (t0.63), with combined measurement probe (rH+T) typ. <6mins (t0.63), for separate T measurement probe
 |  Analog outputs
 
 
    
        
            | 0 to 100% rH/xx to yy°C (for T scaling, see order details)
 | 0 to 1V                                 (-0.5mA < IL <0.5mA) 0 to 5V/0 to 10V                    (-1mA < IL <1mA)
 4 to 20mA (two-wire)             (RL <500ohms)
 |  
            | Temperature sensitivity of the analog outputs | max. 0,2 mV/°C or 1 µA/°C |  Electrical data
 
    
        
            | Supply for 0 to 1V
 0 to 5V
 0 to 10V
 4 to 20mA
 | 10 to 35V DC or 9 - 29V AC
 12 to 35V DC or 15 - 29V AC
 15 to 35V DC or 15 - 29V AC
 10 to 35V DC
 |  
            | Burden (I output) | RL < Uv 10V/0.02A[Ω] |  General information
 
    
        
            | Housing | Al Si 9 Cu 3 |  
            | Probes | stainless steel 1.4305 (reference probes made of PC plastic) |  
            | Dimensions | Housing: 163(135)mm x 90mm x 50mm (W x H x D) (rH/T) probe: 13mm x 91mm (D x L)
 (T) probe (separate): 12(6)mm x 93mm (D x L)
 |  
            | Cable gland | M 16 x1.5 (Lumberg connector option (RSF 50/11)) |  
            | Terminals | Screw terminals for cable cross-sections up to 2.5mm2 |  
            | Housing protection class | IP65 (IP10 for rear cable entry, IP40 for plain wall mounting) |  
            | Ambient temperatures | Measurement probe: -40 to +60°C (+80°C with adapter cable) Electronics: -40 to +60°C
 Storage temperature: -40 to +60°C
 |  
            | Sensor protection | PTFE filter, pore size: 50µm High chemical resistance, response time t0.1/0.9: typ. 14s
 Stainless steel mesh filter (standard),
 for average pollution, high mechanical strength,
 suitable for high humidity applications, response time t0.1/0.9: typ. 7s
 |  
            | Weight | approx. 800g |  
 |