             AXV28-1 
             | 
            
             AXV44-1.5 
             | 
            
             AXV62-1 
             | 
        
        
            | 
             Maximum Output Voltage 
             | 
            
             28kV Peak (20kV RMS) 
             | 
            
             44kV Peak (31kV RMS) 
             | 
            
             62kV Peak (44kV RMS) 
             | 
        
        
            | 
             Output Modes 
             | 
            
             AC Hipot (VLF) Sinusoidal and load independent. DC Hipot (Negative or Positive Polarity). Burn, Cable Fault Conditioning Mode. Sheath/Jacket Testing 
             | 
        
        
            | 
             Maximum Load Capacity, VLF 
             | 
            
             1µF @ 0.1 Hz, Up to 5µF at reduced frequency 
             | 
            
             1.5µF @ 0.1 Hz, Up to 7.5µF at reduced frequency 
             | 
            
             1µF @ 0.1 Hz, Up to 5µF at reduced frequency 
             | 
        
        
            | 
             VLF Test Frequencies 
             | 
            
             Selectable 0.1 Hz, 0.05Hz, 0.02 Hz, 0.01 Hz (Additional Frequencies available upon request) 
             | 
        
        
            | 
             Main Supply 
             | 
            
             120V AC or 240V, 50/60 Hz AC +/- 10% (Operating voltage must be specified at time of purchase) 
             | 
        
        
            | 
             Duty Cycle 
             | 
            
             Continous 
             | 
        
        
            | 
             Environmental 
             | 
            
             -4° F (-20° C) to 113° F (45° C) Humidity non condensing 
             | 
        
        
            | 
             Metering 
             | 
            
             Voltage - True RMS and/or Peak, 0.1kV ± 1%. Current – 0.1mA ± 1% 
             | 
        
        
            | 
             Computer Interface/Memory 
             | 
            
             USB Port – Unlimited Test Record Storage with USB Drives. No Specialized Software Required, Automatic Storage of Results 
             | 
        
        
            | 
             Dimensions H x W x D  
             
            Weight 
             | 
            
             49” (124 cm) x 23” (58 cm) x 25” (64 cm)  
             
            150 lbs (68 kg) 
             | 
            
             49” (124 cm) x 23” (58 cm) x 25” (64 cm) 
             
            177 lbs (80 kg) 
             | 
            
             49” (124 cm) x 26” (66 cm) x 25” (64 cm) 
             
            250 lbs (113 kg) 
             
             
             |