             AXF16- 1280v.2 
             | 
            
             AXF25- 1563v.2 
             | 
            
             AXF28- 1960v.4 
             | 
            
             AXF25- 3126v.4 
             | 
        
        
            | 
             Voltage (adjusted with knob) 
             | 
            
             0-8kV; 0-16kV 
             | 
            
             0-12.5kV; 0-25kV 
             | 
            
             0-14kV; 0-28kV 
             | 
            
             0-12.5kV; 0-25kV 
             | 
        
        
            | 
             Thump Rate 
             | 
            
             Approx. every 10-15 Seconds 
             | 
        
        
            | 
             Energy 
             | 
            
             1280 Joules @ 8kV and 16kV 
             | 
            
             1563 Joules @ 12.5kV and 25kV 
             | 
            
             1960 Joules @ 14kV and 28kV 
             | 
            
             3126 Joules @ 12.5kV and 25kV 
             | 
        
        
            | 
             Burner 
             | 
            
             Optional 
             | 
            
             150mA 
             | 
        
        
            | 
             Weather 
             | 
            
             Operation from -25º F (-31º C) to 110º F (43º C). Unit & Controls sealed for all weather operation. 
             | 
        
        
            | 
             Controls 
             | 
            
             All controls are motorized and operated by toggle switches. 
             | 
        
        
            | 
             12V Internal Battery 
             | 
            
             Standard 
             | 
             | 
        
        
            | 
             120V AC 
             | 
            
             Standard 
             | 
        
        
            | 
             12V DC External 
             | 
            
             Standard 
             | 
             | 
        
        
            | 
             240V AC 
             | 
            
             Optional 
             | 
        
        
            | 
             Dimensions 
             | 
            
             48” (1.2m) Height, 29.5” (75cm) Wide 
             | 
        
        
            | 
             Weight 
             | 
            
             230 Lbs. (105kg) 
             | 
            
             250 Lbs (114kg) 
             | 
            
             250 Lbs (114kg) 
             | 
            
             340 Lbs. (154kg) 
             | 
        
        
            | 
             Leads 
             | 
            
             50’ (15.25m) Shielded HV Lead terminated in Male MC Connector and a 15’ (4.5m) #2 Ground Cable are standard. Cable Reel Systems, EPR-X-ray Cable HV Leads and Custom Lengths are also Available. 
             | 
        
        
            | 
             HV Coupler/Filter 
             | 
            
             An inductive filter is used to minimize distortion and energy loss. 
             | 
        
        
            | 
             TDR Specifications 
             | 
            
             v.2 Monochrome 
             | 
            
             v.4 Color 
             | 
        
        
            | 
             Auto Analyze 
             | 
            
             Automatically marks end of cable and fault location and gives distance. 
             | 
        
        
            | 
             Screen 
             | 
            
             3.5” (8.9cm) x 4.5” (11.4cm) LCD (320x240) – Backlight Visible in Bright Light 
             | 
            
             10.5" diagonal (243mm x 185.1mm) color TFT LCD – Backlight Visible in Sun Light 
             | 
        
        
            | 
             Environmental 
             | 
            
             Radar contained within the sealed case of the thumper allowing all weather operation. Operable from -25ºF (-31ºC) to 110ºF (43ºC). 
             | 
            
             Radar contained within the sealed case of the thumper allowing all weather operation. Operable from 20ºF (-7ºC) to 120ºF (49ºC). 
             | 
        
        
            | 
             Accuracy 
             | 
            
             0.5% of the range selected 
             | 
        
        
            | 
             Memory 
             | 
            
             9 Memories available. Software is also available for downloading traces to a Laptop 
             | 
            
             15 Memories available. Software is also available for downloading traces to a Laptop 
             | 
        
        
            | 
             Additional Features 
             | 
            
             3 phase display, Current Impulse Method (CIM) available as options 
             
             
             |