- Extremely stable with low detection limit at 6 ppb
- Suitable for trace SF6 leak detection, with up to 24 channel multiplexing possible
- Capable of measuring up to 3x the maximum allowable concentration (MAC = 1000 ppm for SF6)
- System designed to minimize interference from vibration, and automatically compensate for temper-ature, pressure, and humidity interference.
Thông số kỹ thuật
    
        
            | Detection Principle | 
            Photoacoustic Infrared Spectroscopy | 
        
        
            | Detection Limit | 
            6 ppb (standard) | 
        
        
            | Response Time | 
            27s (Standard Mode); 13s (Fast Mode) | 
        
        
            | Dynamic Range | 
            5 - 50,000 ppb (50 ppm) Standard; 1 - 4,000 ppm Optional | 
        
        
            | Repeatability | 
            1% of Measured Value | 
        
        
            | Zero Drift | 
            ± Detection Limit per Quarter | 
        
        
            | Influence of temperature | 
            ±10% of Detection Limit per ˚C | 
        
        
            | Influence of presure | 
            ±0.5% of Detection Limit per mbar | 
        
        
            | Range Drift | 
            ±2.5% of Measured Value per Quarter | 
        
        
            | Influence of temperature | 
            ±0.3% of Measured Value per ˚C | 
        
        
            | Influence of pressure | 
            -0.01% of Measured Value per mbar |