             AXF16- 1280TP 
             | 
            
             AXF28- 1960TP 
             | 
            
             AXF25- 3126TP 
             | 
            
             AXF28- 3920TP 
             | 
            
             AXF32- 5120TP 
             | 
            
             AXF36- 6480TP 
             | 
            
             AXF36- 7614TP 
             | 
        
        
            | 
             Voltage (adjusted with knob) 
             | 
            
             0-8kV; 
             
            0-16kV 
             | 
            
             0-14kV; 
             
            0-28kV 
             | 
            
             0- 12.5kV; 
             
            0-25kV 
             | 
            
             0-14kV; 
             
            0-28kV 
             | 
            
             0-8kV; 0-16kV; 
             
            0-32kV 
             | 
            
             0-9kV; 0-18kV;0-36kV 
             | 
        
        
            | 
             Thump Rate 
             | 
            
             Approx. every 10 Seconds 
             | 
        
        
            | 
             Energy 
             | 
            
             1280 Joules @ 
             
            8kV and 16kV 
             | 
            
             1960 Joules @ 
             
            14kV and 28kV 
             | 
            
             3126Joules @ 
             
            12.5kV and 25kV 
             | 
            
             3920 Joules @ 
             
            14kV and 28kV 
             | 
            
             5120 Joules @ 
             
            8kV,16kV and 32kV 
             | 
            
             6480 Joules @ 9kV,18kV and 36kV 
             | 
            
             7614 Joules @ 9kV,18kV and 36kV 
             | 
        
        
            | 
             Weather 
             | 
            
             Operation from -20ºF (-29º C) to 131ºF (55ºC). Unit & Controls sealed for all weather operation. 
             | 
        
        
            | 
             Controls 
             | 
            
             All controls are motorized and operated by toggle switches. 
             | 
        
        
            | 
             Input Power 
             | 
            
             120V AC Standard (240V AC Optional) 
             | 
        
        
            | 
             Weight 
             | 
            
             230 Lbs. (105kg) 
             | 
            
             250 Lbs (114kg) 
             | 
            
             340 Lbs (155kg) 
             | 
            
             340 Lbs. (155kg) 
             | 
            
             540 Lbs. (245kg) 
             | 
             | 
             | 
        
        
            | 
             Leads 
             | 
            
             25’ (7.6m) Shielded HV Lead terminated in Male MC Connector and a 25’ (7.6m) #2 Ground Cable are standard to interface a Cable Reel System. 125’ (38m) and 200’ (61m) Cable Reel Systems are available. Cables from Thumper to Control/TDR 15’ (4.5m) 
             | 
        
        
            | 
             HV Coupler/Filter 
             | 
            
             An inductive filter is used to minimize distortion and energy loss. 
             | 
        
        
            | 
             Burner 
             | 
            
             140mA 
             | 
            
             100mA 
             | 
            
             150mA 
             | 
            
             150mA 
             | 
            
             250mA 
             | 
            
             300mA 
             | 
        
        
            | 
             Hi Pot 
             | 
            
             1ma, 10mA Current Measurement to full voltage (optional) 
             | 
        
        
            | 
             TDR Specifications 
             | 
            
             v.2 Monochrome 
             | 
            
             v.4 Color 
             | 
        
        
            | 
             Auto Analyze 
             | 
            
             Automatically marks end of cable and fault location and gives distance 
             | 
        
        
            | 
             Screen 
             | 
            
             3.5” (8.9cm) x 4.5” (11.4cm) LCD with 320x240 dot matrix – Backlight Visible in Bright Light 
             | 
            
             10.5" diagonal (243mm x 185.1mm) color TFT LCD –Backlight Visible in Sun Light 
             | 
        
        
            | 
             Environmental 
             | 
            
             Radar contained within the sealed case of the thumper allowing all weather operation. Operable from -25ºF (-31ºC) to 131ºF (55º C). 
             | 
            
             Radar contained within the sealed case of the thumper allowing all weather operation. Operable from 20ºF (-7º C) to 131ºF (55ºC). 
             | 
        
        
            | 
             Accuracy 
             | 
            
             0.5% of the range selected 
             | 
        
        
            | 
             Memory 
             | 
            
             9 Memories available. Software is also available for downloading traces to a Laptop 
             | 
            
             15 Memories available. Software is also available for downloading traces to a Laptop 
             | 
        
        
            | 
             Additional Features 
             | 
            
             3 phase display, Current Impulse Method (CIM) available as options 
             
             
             |