| Types of Data Logger Inputs | 
        
        
            | Measured values | 
            Range | 
            Accuracy | 
            Note | 
        
        
            | Current | 
            DC | 
            4 to 20 mA | 
            ±0.1% FS (±0.02mA) | 
            it is possible to connect pasive sensors (powered by monitoring system) or active sensor with its own power supply. Input resistance about 110 Ohms. | 
        
        
            | Voltage | 
            DC | 
            -10V to +10V | 
            ±0.1% FS (±10 mV) | 
            input resistance about 10MOhms | 
        
        
            | -1V to +1V | 
            ±0.1% FS (±1 mV) | 
        
        
            | -100mV to +100mV | 
            ±0.1% FS (±100 uV) | 
        
        
            | -18mV to +18mV | 
            ±0,1% FS (±18 uV) | 
        
        
            | Resistance | 
            two-wire resistance measurement | 
            0 to 300 Ohms | 
            ±0.1% FS (±0.3 Ohm) | 
            measuring current approximately 0.8 mA @ 50ms pulse | 
        
        
            | 0 to 3000 Ohms | 
            ±0.1% FS (±3 Ohm | 
            measuring voltage approximately 0.5mA @ 50ms pulse | 
        
        
            | 0 to 10000 Ohms | 
            ±0.1% FS (±10 Ohm) | 
            measuring current approximately 0.1mA @ 50ms pulse | 
        
        
            | Temperature probes Pt and Ni | 
            Ni1000 | 
            -50°C to +250°C | 
            ±0.2°C (-50°C to 100°C) | 
            Ni1000/6180 ppm, two-wire connection | 
        
        
            | ±0.2% MH (100°C to 250°C) | 
            measuring current approximately 0.5mA @ 50ms pulse | 
        
        
            | Pt100 | 
            -200°C to +600°C  | 
            ±0.2°C (-200°C to+100°C) | 
            Pt100/3850 ppm, two-wire connection | 
        
        
            | ±0.2% MH (+100°C to +600°C) | 
            measuring current approximately 0.8mA @ 50ms pulse | 
        
        
            | Pt1000 | 
            -200°C to +600°C | 
            ±0.2°C (-200°C to+100°C) | 
            Pt1000/3850 ppm, two-wire connection | 
        
        
            | ±0.2% MH (+100°C to +600°C) | 
            measuring current about 0.5mA @ 50ms pulse | 
        
        
            | Thermistor | 
            NTC with selectable formula | 
            up to maximum thermistor resistance 11000 Ohms | 
            according to the used resistance range (see measurement of resistance) | 
            the same characteristics for all connected thermistors. 
            Default settings: R25=2252Ω, R80=282.7Ω | 
        
        
            | Thermocouple | 
            K (NiCr-Ni) | 
            -200°C to 1300°C | 
            ±0.3% MH +1.5°C | 
            linearized, with cold junction compensation, datalogger must be placed in recommendend working position | 
        
        
            | T (Cu-CuNi) | 
            -200°C to 400°C | 
        
        
            | J (Fe-Co) | 
            -200°C to 750°C | 
        
        
            | S (Pt10%Rh-Pt) | 
            0 to 1700°C | 
        
        
            | N (NiCrSi-NiSiMg) | 
            -200°C to 1300°C | 
        
        
            | B (Pt30%Rh-Pt) | 
            100°C to 1800°C | 
            ±0.3% MH+1.0°C (300°C to 1800°C) | 
            linearized without cold junction compensation | 
        
        
            | Binary signal | 
            potential-less contact | 
            binary signal | 
            input voltage for state "L" (IN-COM) < 0.8 V | 
        
        
            | input voltage for state "H" (IN-COM) > 2 V | 
        
        
            | open collector | 
            resistance of closed contact for state "L" (IN-COM) < 1 kOhms | 
        
        
            | voltage levels | 
            resistance of closed contact for state "H" (IN-COM) > 10 kOhms | 
        
        
            | minimum duration for sensing of change: 200ms | 
        
        
            |  RS485 | 
            input for serial signal RS485 | 
            on request | 
            input serves for reading from devices supporting protocol ModBus RTU or Advantech | 
        
        
            | connected to terminals next to terminals for channel 15 and 16 | 
        
        
            | input can work with 16 devices | 
        
        
            | Galvanically isolated. |